This new-generation scroll-type water-source heat pump is built for industrial hot water needs up to 85°C. The brochure describes a COP of 4.0–4.5, energy savings above 60%, cloud-platform support, fault and status logging, and broad application in hospitals, hotels, offices, brewing, petrochemical, and pharmaceutical settings. It is also presented as compact, reliable, easy to install, and environmentally friendly.
Key Features:
·Basic model: 112/224/336kW
·Modular design for flexible combination
·High efficency: COP up to 4.5
·Waste heat recovery and recycling
·7 inch touchscreen controller and easy operation
·Intelligent control: Real-time monitoring of unit operating parameters and self-diagnosis function.
The unit is built to supply stable high-temperature hot water where standard heat pumps struggle to meet process requirements.
2. Efficient Operation with Lower Energy Use
With a COP of 4.0–4.5, it offers a strong balance between performance and operating cost.
3. Cloud-Connected, Easy to Manage
Cloud-platform functions, fault logging, and operating-status recording for smarter maintenance.
4. Flexible, Space-Saving Installation
Its compact structure makes it suitable for both retrofit and new-build projects with tighter installation constraints.
Specification
Model
LSR110A-G
LSR220A-G
LSR330A-G
Heating Capacity
kW
112
224
336
Rated Input Power
kW
31.1
62.2
93.3
Rated Current
A
52.9
105.8
158.7
Compressor
Nominal Power
HP
25
50
75
Condenser
Water Flow
m³/h
19.3
38.5
57.8
Connection Size
mm
DN65
DN80
DN100
Water Pressure Drop
kPa
45
48
50
Evaporator
Water Flow
m³/h
13.9
49.2
73.8
Connection Size
mm
DN65
DN80
DN100
Water Pressure Drop
kPa
45
47
48
Refrigerant
Type
/
R134a
Charge Amount
kg
20
40
60
Unit Dimensions
Length
mm
2400
2851
3371
Width
mm
911
911
911
Height
mm
1418
1412
1466
Weight
kg
1000
1200
1400
Note:
1.The parameters in the above table are based on the following operating conditions: User side water inlet/outlet temperature 75/80°C, Heat source side water inlet/outlet temperature 45/40°C.
2.The water side pressure rating is 1.6MPa; please specify if a higher pressure is required.
3.The unit parameters in the above table are for standard models. For non-standard parameter requirements, please contact Shenmei Company sales for consultation.
Figure: 85℃ High Temperature Scroll Water Source Heat Pump Unit outline drawing